Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 55

55
Defaults
Group
Locks/ Range Description
Single Synch- Multi- Constant Speed
10
Passwords
Pump ronous Control Slave Control
1004 Parameter Save Save
Used for manually saving
Done Done
Done
Done
Done
(continued)
parameters that have been
altered through the fieldbus
connection.
1005 New Pass Code 0…300000
Sets new pass code for
0
0
0
0
0
parameter lock. Returns to 0
after saving.
1006 Set Point Lock
Disables set point changes
Off
Off
Off
Off
Off
from the keypad.
Off (Default) Local control allowed.
On
Local control allowed.
Group
Start-Up
Range Description
Single Synch- Multi- Constant Speed
11
Data
Pump ronous Control Slave Control
1101 Language
Selects the display language
English English English
English
English
English (AM)
American English.
(Default)
Español
Spanish (full translation)
Francais
French (full translation)
1102 Application
Selects the application macro
✔
✔
✔
✔
✔
Macro
Single Pump
One AV regulating to a set point
(Default)
Synchronous
Lag pumps start as needed and
all pumps regulate to the set
point at the same speed. Note:
it is recommended that all
pumps be identical.
Multicontrol
Lag pumps start as needed. The
last lag pump to start regulates
to the set point; the remaining
pumps operate at an enable
sequence speed (2203).
Constant Slave The master unit starts up to
three fixed speed slave units
when needed. See RO1, RO2
and RO3 settings (parameters
1801, 1804 and 1807).
Speed Control AV follows a speed reference
only. Pump protect fault
function is inactive.
1103 Application
No
Resets parameters to default
Restore
Yes
settings.
PARAMETER LISTINGS