Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 65

65
Defaults
Group
Analog Range Description
Single Synch- Multi- Constant Speed
19
Outputs
Pump ronous Control Slave Control
1904 Minimum AO1
0.0…20.0 mA Defines the minimum value of
0.1
0.1
0.1
0.1
0.1
AO1. Default = 4 mA.
1905 Maximum AO1
0.0…20.0 mA Defines the maximum value of
20
20
20
20
20
AO1. Default = 20 mA.
1906 AO 2 Content Sel
Connects a AV signal to analog
Not
Not
Not
Not
Not
output 2 (AO2).
Used
Used
Used
Used
Used
Not Sel (default) Not in use.
Frequency
Output frequency. 20 mA =
motor nominal frequency (1106).
Current
Output current. 20 mA =
motor nominal current (1105).
Torque
Motor torque. 20 mA = 100%
of motor nominal rating.
Power
Motor Power. 20 mA = 100%
of motor power rating.
Proc Var/
Actual value of process variable
Actual
AI2. 20 mA = Reference 1 Max
(1603).
Energy Saving Calculated energy savings
(option 1 or 2) over a conven-
tional fixed speed system.
20 mA = Savings scale (2603).
1907 AO2 Content
Various
Selects the minimum value of the
Min
characterisitc being monitored.
1908 AO2 Content
Various
Selects the maximum value of the
Max
characteristic being monitored.
1909 Minimum AO2
0.0…20.0 mA Defines the minimum value of
4
4
4
4
4
AO2. Default = 4 mA
1910 Maximum AO2
0.0…20.0 mA Defines the maximum value of
20
20
20
20
20
AO2. Default = 20 mA
Group
Regulate Range
Description
Single Synch- Multi- Constant Speed
21
Pump ronous Control Slave Control
2101 Regulation Mode
Selects the type of AV control with Normal Normal Normal Normal Normal
falling process variable signal.
Normal
Increases the output speed with
(Default)
falling process variable signal.
For level control applications the
tank is on the discharge side.
Inverse
Decreases the output speed with
falling process variable signal.
For level control applications the
tank is on the suction side.
PARAMETER LISTINGS