MultiPump – Slave Pump Control
21. Once previous step has been saved, use the Down Arrow
and highlight parameter “2203 ENABLE SEQUENCE”, then
press EDIT. Using the up or down arrow, enter the frequency
in Hertz (HZ) that you wish the SLAVE pump will turn on once
the lead pump reaches this speed. Default is set for 59 HZ
and is typical for 60HZ systems. If you change this setting,
press the SAVE key. If no changes are required, then press
the EXIT key.
22. Group 2205 – Enter frequency for slave pump to be turned off.
23. Final step is to enter your required pressure in
the system. After above programming has been
completed, press the EXIT key two (2) or three
(3) times, until you arrive back to the first control
display screen. (SEE DIAGRAM) Then press the
UP or DOWN arrow to select the required system
pressure for your Aquavar controlled pump. Once
pressure has been selected, press the green
START key on the keypad.
24. Optional Step: To lock out access to the control
panel (keypad), refer to page 104. This will prevent
unauthorized users from changing programming.
NOTE: If an error or fault occurs, refer to the faults/alarms section of this manual, page
115. When troubleshooting an Aquavar system, always break down into the following
components:
1. Aquavar programming — check default settings recommended for single pump, multi-
pump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding — check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation — check your pump rotation, rubbing or other mechanical
problems. Pump “ run out”.
4. Hydraulic System/ Piping — check to ensure proper suction and ischarge piping layout,
proper NPSHa, air entrainment, vortex, friction loss, system curve compensation etc.
5. Environment — protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.
EXIT
EDIT
REM
PARAMETERS
2201 VALUE DECREASE
2202 VALUE INCREASE
2203 ENABLE SEQUENCE
59.00 HZ
2204 SWITCH LEAD/LAG
PROGRAMMING
DIR
MENU
REM
27.8%
LOC
REM
Status
LED
UP
SOFT
KEY 1
DOWN
LOC/REM
STOP
START
HELP
SOFT
KEY 2
40.2 PSI
sp
0.0 PSI
ac
0.0 HZ