Parameter listings – Xylem IM167 R8 Aquavar CPC (Centrifugal Pump Control) User Manual
Page 69

69
Defaults
Group
Fault Range Description
Single Synch- Multi- Constant Speed
24
Functions
Pump ronous Control Slave Control
2409 Comm Fault
Selects how the drive reacts in a Last
Last
Last
Last
Last
Function
fieldbus comm break i.e.; if the Speed Speed Speed
Speed
Speed
drive fails to receive command
word or reference. The time de-
lays is given by parameter 2410.
Not Selected No response
Fault
Drive Faults and coasts to stop
Last Speed
Drive displays a warning and
remains running at last speed
reference.
2410 Comm Fault
0…60.0s
Defines the time delay for the
3.0 s
3
3
3
3
Time
control word or reference
supervision.
Group
Automatic
Range Description
Single Synch- Multi- Constant Speed
25
Reset
Pump ronous Control Slave Control
2501 NR of Trials
0…5
Sets the number of allowed
0
0
0
0
0
automatic resets within a trial
period defined by parameter
2502.
2502 Trial Time
1.0…600.0 s
Sets the time limit used for
30 s
30 s
30 s
30 s
30 s
counting and limiting the
number of resets.
2503 Delay Time
0.0…120.0 s
Sets the delay between fault
0 s
0 s
0 s
0 s
0 s
detection and attempted drive
restart.
2504 AR Overcurrent
Auto reset after overcurrent
Enabled Enabled Enabled Enabled Enabled
Disable
fault.
2505 AR Overvoltage
Auto reset of overvoltage
Enabled Enabled Enabled Enabled Enabled
Disable
fault.
2506 AR Undervoltage
Auto reset for undervoltage
Enabled Enabled Enabled Enabled Enabled
Disable
of drive.
2507 AR AI Auto reset after transducer Enabled Enabled Enabled Enabled Enabled Disable signal loss. Group Energy Range Description Single Synch- Multi- Constant Speed 26 Savings Pump ronous Control Slave Control 2601 Energy Cost 0.000…1.000 Cost of energy in USD 2602 Baseline Power 0…1000 hp Baseline HP for a conventional fixed speed system. 2603 Savings Scale 0…65535 This parameter scales the 10000 10000 10000 10000 10000 analog output when energy savings is selected. 2604 Energy Save Savings Savings Savings Savings Savings Methd Savings Op 1 Op 1 Op 1 Op 1 Op 1 Op 1 Savings Op 2 PARAMETER LISTINGS