Single point functions
66
5
5.2 Single Point Relay protection
Entellisys system provides Single Point Protection Relay functions in three optional packages: 
the Voltage Relays package, the Frequency and Reverse Power Relays package and the High 
Current Relay package.
The Voltage Relays package includes the following functions:
•
Undervoltage
•
Overvoltage
•
Phase Loss Protection
The Frequency and Reverse Power Relays package includes the following functions:
•
Under Frequency
•
Over Frequency
•
Reverse Power Protection
The High Current Relay package includes the following function:
•
High Current Protection
NOTE: Removing a relay package from a Messenger can cause any control scheme that 
includes those relays to misoperate. See 
for more details.
These protection relay functions run in addition to the standard overcurrent protection 
functions and are performed at the Entellisys CPU only. No protection relay functions are 
performed locally at the Messengers.
Each relay has two sets of pickup and delay settings, with the exception of the High Current and 
High Resistance GF. One set is for tripping the circuit breaker and the other is for activating an 
alarm. Therefore, a user can set one threshold for a trip condition and the other threshold for an 
alarm condition. It is possible to enable or disable each relay function individually; for example, it 
is possible to enable a relay alarm function but disable the trip function.