GE Industrial Solutions Entellisys 4.0 System User Manual User Manual
Page 258

Alarms and events
258
A
Alarm High Current Trigger
Logged when function operated
Messenger/Breaker Config Status
Caution Messngr Control Power 
1 Lost
Messenger reports that it has lost control 
power source 1
•
Check LINE LED on UPS. If it is off, check 
the main power switch on the UPS. If it is 
off, turn it on. Otherwise, check the 
control power fuse between the 
transformer and the UPS.
•
If the LINE LED is on, check the ON LINE 
LED. If it is off, see the UPS manual.
•
Check UPS fuse.
•
Contact GE Post Sales Service (see
).
Caution Messngr Control Power 
2 Lost
Messenger reports that it has lost control 
power source 2
Same as control power 1 lost
Messngr Control Power 1 OK
Messenger reports that control power source 
1 is present
Messngr Control Power 2 OK
Messenger reports that control power source 
2 is present
Note Invalid Breaker Type
Messenger reports a breaker type other than 
ANSI
Compartment ID button has been 
misconfigured, contact GE Post Sales Service 
(see 
Protection Defaulted Invalid 
Frame Rating
Messenger reports a frame rating value that 
is not valid, protection settings set to values 
that are safe for all frame sizes
Compartment ID button has been 
misconfigured, contact GE Post Sales Service 
(see 
Protection Defaulted Invalid CT 
Rating
Messenger reports a CT rating value that is 
not valid, protection settings set to values 
that are safe for all frame sizes
Compartment ID button has been 
misconfigured, contact GE Post Sales Service 
(see 
Protection Defaulted Frame And 
CT Mismatch
Messenger reports frame and CT ratings that 
are inconsistent, protection settings set to 
values that are safe for all frame sizes
Compartment ID button has been 
misconfigured, contact GE Post Sales Service 
(see 
Protection Defaulted Invalid 
Rating Switch
Messenger reports a rating switch value that 
is not valid, protection settings set to values 
that are safe for all frame sizes
Contact GE Post Sales Service (see
).
Attention Check Switch Invald LT 
Overcurrent Set
Messenger reports a long time overcurrent 
protection pickup setting that is not valid
Contact GE Post Sales Service (see
).
Caution Enet Cable 
Disconnected Messngr CPUA
Messenger reports that it has no ethernet 
connection to CPU A
Check connection between CPU A and 
switch, and the switch and the Messenger.
Caution Enet Cable 
Disconnected Messngr CPUB
Messenger reports that it has no ethernet 
connection to CPU B
Check connection between CPU B and 
switch, and the switch and the Messenger.
Attention Messngr Synch 
Disabld Bad Freq CPUA
Messenger has received an invalid system 
frequency from CPU A and will not be able to 
synchronize from it
Contact GE Post Sales Service (see
).
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips
