Alarms and events
258
A
Alarm High Current Trigger
Logged when function operated
Messenger/Breaker Config Status
Caution Messngr Control Power
1 Lost
Messenger reports that it has lost control
power source 1
•
Check LINE LED on UPS. If it is off, check
the main power switch on the UPS. If it is
off, turn it on. Otherwise, check the
control power fuse between the
transformer and the UPS.
•
If the LINE LED is on, check the ON LINE
LED. If it is off, see the UPS manual.
•
Check UPS fuse.
•
Contact GE Post Sales Service (see
).
Caution Messngr Control Power
2 Lost
Messenger reports that it has lost control
power source 2
Same as control power 1 lost
Messngr Control Power 1 OK
Messenger reports that control power source
1 is present
Messngr Control Power 2 OK
Messenger reports that control power source
2 is present
Note Invalid Breaker Type
Messenger reports a breaker type other than
ANSI
Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see
Protection Defaulted Invalid
Frame Rating
Messenger reports a frame rating value that
is not valid, protection settings set to values
that are safe for all frame sizes
Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see
Protection Defaulted Invalid CT
Rating
Messenger reports a CT rating value that is
not valid, protection settings set to values
that are safe for all frame sizes
Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see
Protection Defaulted Frame And
CT Mismatch
Messenger reports frame and CT ratings that
are inconsistent, protection settings set to
values that are safe for all frame sizes
Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see
Protection Defaulted Invalid
Rating Switch
Messenger reports a rating switch value that
is not valid, protection settings set to values
that are safe for all frame sizes
Contact GE Post Sales Service (see
).
Attention Check Switch Invald LT
Overcurrent Set
Messenger reports a long time overcurrent
protection pickup setting that is not valid
Contact GE Post Sales Service (see
).
Caution Enet Cable
Disconnected Messngr CPUA
Messenger reports that it has no ethernet
connection to CPU A
Check connection between CPU A and
switch, and the switch and the Messenger.
Caution Enet Cable
Disconnected Messngr CPUB
Messenger reports that it has no ethernet
connection to CPU B
Check connection between CPU B and
switch, and the switch and the Messenger.
Attention Messngr Synch
Disabld Bad Freq CPUA
Messenger has received an invalid system
frequency from CPU A and will not be able to
synchronize from it
Contact GE Post Sales Service (see
).
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips