beautypg.com

GE Industrial Solutions Entellisys 4.0 System User Manual User Manual

Page 258

background image

Alarms and events

258

A

Alarm High Current Trigger

Logged when function operated

Messenger/Breaker Config Status

Caution Messngr Control Power
1 Lost

Messenger reports that it has lost control
power source 1

Check LINE LED on UPS. If it is off, check
the main power switch on the UPS. If it is
off, turn it on. Otherwise, check the
control power fuse between the
transformer and the UPS.

If the LINE LED is on, check the ON LINE
LED. If it is off, see the UPS manual.

Check UPS fuse.

Contact GE Post Sales Service (see

How

to contact us on page 2

).

Caution Messngr Control Power
2 Lost

Messenger reports that it has lost control
power source 2

Same as control power 1 lost

Messngr Control Power 1 OK

Messenger reports that control power source
1 is present

Messngr Control Power 2 OK

Messenger reports that control power source
2 is present

Note Invalid Breaker Type

Messenger reports a breaker type other than
ANSI

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Invalid
Frame Rating

Messenger reports a frame rating value that
is not valid, protection settings set to values
that are safe for all frame sizes

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Invalid CT
Rating

Messenger reports a CT rating value that is
not valid, protection settings set to values
that are safe for all frame sizes

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Frame And
CT Mismatch

Messenger reports frame and CT ratings that
are inconsistent, protection settings set to
values that are safe for all frame sizes

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Invalid
Rating Switch

Messenger reports a rating switch value that
is not valid, protection settings set to values
that are safe for all frame sizes

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Check Switch Invald LT
Overcurrent Set

Messenger reports a long time overcurrent
protection pickup setting that is not valid

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Caution Enet Cable
Disconnected Messngr CPUA

Messenger reports that it has no ethernet
connection to CPU A

Check connection between CPU A and
switch, and the switch and the Messenger.

Caution Enet Cable
Disconnected Messngr CPUB

Messenger reports that it has no ethernet
connection to CPU B

Check connection between CPU B and
switch, and the switch and the Messenger.

Attention Messngr Synch
Disabld Bad Freq CPUA

Messenger has received an invalid system
frequency from CPU A and will not be able to
synchronize from it

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips