Alarms
202
13
13.2.1 Alarm Emails
Emails can be sent when any of the 24 configurable alarms occur. The emails are sent using 
standard Simple Mail Transport Protocol (SMTP). Up to 4 recipients can be listed as email 
recipients and each alarm can be configured to email any of the 4 recipients.
Alarm emails can only be configured at a Local HMI (Kiosked Panel C) and if there are more than 
one local HMI, one must be designated as the master, see chapter 4.2 in the System 
Administrator Manual, DEH-430 for more details. The Lineup must also be configured to 
communicate on a LAN for email notifications to reach a SMTP server, see chapter 6 in the 
System Administrator Manual, DEH-430 for more details.
Figure 13-2 Alarms Setup screen
To configure the SMTP server used for e-mail notifications, select the Email Preferences tab on 
the Alarms screen. Server information is typically available from an IT Systems Administrator at 
the plant location. A test e-mail address feature is provided to assist in testing e-mail 
functionality once it is set up.
The Email Preferences tab on the Alarms screen also includes a field for specifying Email 
Notification on Control Power Events. Control power events are associated with the 
uninterruptible power supplies that power the Entellisys Control Power Network, and may be 
used to warn of an extended outage of the Entellisys system.