GE Industrial Solutions Entellisys 4.0 System User Manual User Manual
Page 246

Alarms and events
246
A
Attention: CPU Firmware Version
Mismatch between CPUA and
CPUB
The firmware revisions are not consistent
between the primary and redundant CPUs.
Check the CPU Firmware tab under the
maintenance menu, or contact GE Post Sales
Service (see
Note that a sufficient privilege level is
required to perform this operation.
CPUA Commissioned
CPU A transitioned from the decommissioned
state to the commissioned state.
CPUB Commissioned
CPU B transitioned from the decommissioned
state to the commissioned state.
CPUA Decommissioned
CPU A transitioned from the commissioned
state to the decommissioned state.
Contact GE Post Sales Service if this occurs
when not expected (see
).
CPUB Decommissioned
CPU B transitioned from the commissioned
state to the decommissioned state.
Contact GE Post Sales Service if this occurs
when not expected (see
).
Command and Control Power Related
Breaker Close Command Issued
from HMI For [Breaker Name]
Logged when an operator issues a close
command for a given breaker
Breaker Open Command Issued
from HMI For [Breaker Name]
Logged when an operator issues an open
command for the specified breaker
Breaker Trip Command Issued
from HMI For [Breaker Name]
Logged when an operator issues a trip
command for the specified breaker
[Alarm Name] Is In Alarm
Condition
The specified alarm has entered the active
condition.
Attention: Control Power 1
Outage Detected On Battery
Backup
The primary control power source has
experienced an outage and is now operating
from the UPS battery backup.
Attention: Control Power 1 Low
Battery Detected Shutdown in 2
mins
The HMI will shutdown in the specified
amount of time due to impending outage of
the UPS battery backup.
Control Power 1 Power Restored Power has been restored to the primary
control power bus.
RELT
Logged by HMI when user initiates RELT
Multipoint RELT
Logged by HMI when user turns off RELT
CPU-Related Events
These events are generated within the CPU
and retrieved by the HMI via
communications.
Relays – Voltage
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips