FlexLogic™
178
11
Some operands can be renamed by the user. The operands that can be renamed are the names 
of contact inputs/outputs and virtual inputs/outputs. If the user changes the default name of 
any of these operands, the assigned name appears in the relay list of operands. The default 
names are shown in the FlexLogic operands table (Table 11-2).
The operators available in FlexLogic are listed in Table 11-3.
Table 11-3 FlexLogic operators
Type
Syntax
Descriptions
Notes
Editor
Copy
Copy a parameter from an equation list.
Paste
Paste a parameter in an equation list.
Insert
Insert a parameter in an equation list.
Delete
Delete a parameter from an equation list.
End
END
The first END encountered signifies the 
last entry in the list of processed 
FlexLogic parameters.
One Shot
POSITIVE ONE SHOT One shot that responds to a positive
going edge.
A 'one shot' refers to a 
single input gate that 
generates a pulse in 
response to an edge on the 
input. The output from a 
'one shot' is True (positive) 
for only one pass through 
the FlexLogic equation. 
There is a maximum of 64 
'one shots'.
NEGATIVE ONE 
SHOT
One shot that responds to a negative 
going edge.
DUAL ONE SHOT
One shot that responds to both the 
positive and negative going edges.