GE Industrial Solutions Entellisys 4.0 System User Manual User Manual
Page 266

Alarms and events
266
A
CPU Updates (firmware & options)
CPU Firmware Download
Started
CPU firmware download process started
CPU Firmware Download
Complete
New firmware has been downloaded to CPU
Upgrade Successful
New option string successfully downloaded
to CPU
Upgrade Failure Internal Error 2 CPU detected an internal error during the
option upgrade process
Contact GE Post Sales Service (see
).
Upgrade Failure Internal Error 3 CPU detected an internal error during the
option upgrade process
Contact GE Post Sales Service (see
).
Upgrade Failure Internal Error 4 CPU detected an internal error during the
option upgrade process
Contact GE Post Sales Service (see
).
Upgrade Failure Option String
Corrupt
Invalid or corrupted option string: incorrect
option string format
Contact GE Post Sales Service (see
).
Upgrade Failure Unable To
Decrypt
Invalid or corrupted option string: decryption
failure or bad digital signature
Contact GE Post Sales Service (see
).
Upgrade Failure Due To Bad
CRC
Invalid or corrupted option string: bad CRC
Contact GE Post Sales Service (see
).
Upgrade Failure Hardware
Mismatch
Invalid or corrupted option string: MAC
address mismatch
Contact GE Post Sales Service (see
).
CPU Firmware Failure Previous
Version In Use
CPU firmware upgrade operation failed; CPU
is using previous firmware version
Contact GE Post Sales Service (see
).
Attention New Messngr Options
Deficient
More per-breaker options are enabled then
the number available per the option string.
This can occur when a new option string is
loaded that contains fewer per-breaker
options than the original option string.
The CPU will allocate the options to the
lowest numbered breakers that have the
option specified. For metering options,
allocate the available meters to the desired
breakers. For relaying options, contact GE
Post Sales Service (see
).
Preventative Maintenance
Breaker In Service Anniversary
Breaker anniversary date has been reached
Breaker Mechanical Life At XX
Percent
See section on Preventative Maintenance
Breaker Load Life At XX Percent See section on Preventative Maintenance
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips