GE Industrial Solutions Entellisys 4.0 System User Manual User Manual
Page 259

Alarms and events description and system troubleshooting guide
259
A
Attention Messngr Synch
Disabld Bad Freq CPUB
Messenger has received an invalid system
frequency from CPU B and will not be able to
synchronize from it
Contact GE Post Sales Service (see
).
Invalid Setting IOC Mult CPUA
Chng Rejected
Messenger has received an invalid IOC
pickup setting from CPU A and has rejected
the value
This event is recorded by CPU B based on
status information sent to the Messenger by
CPU A. The Sequence of Events for CPU A
should have an “Invalid Setting IOC Change
Rejected” or “Invalid Setting IOC Pickup
Change Rejected” event. See the description
of those events for details.
Invalid Setting IOC Mult CPUB
Chng Rejected
Messenger has received an invalid IOC
pickup setting from CPU B and has rejected
the value
This event is recorded by CPU A based on
status information sent to the Messenger by
CPU B. The Sequence of Events for CPU B
should have an “Invalid Setting IOC Change
Rejected” or “Invalid Setting IOC Pickup
Change Rejected” event. See the description
of those events for details.
Invalid Setting ST From CPUA
Change Rejected
Messenger has received an invalid short time
enable or disable setting from CPU A and has
rejected the value
This event is recorded by CPU B based on
status information sent to the Messenger by
CPU A. The Sequence of Events for CPU A
should have an “Invalid Setting ST Change
Rejected” or “Invalid Setting ST Pickup
Change Rejected” event. See the description
of those events for details.
Invalid Setting ST From CPUB
Change Rejected
Messenger has received an invalid short time
enable or disable setting from CPU B and has
rejected the value
This event is recorded by CPU A based on
status information sent to the Messenger by
CPU B. The Sequence of Events for CPU B
should have an “Invalid Setting ST Change
Rejected” or “Invalid Setting ST Pickup
Change Rejected” event. See the description
of those events for details.
Invalid Setting GF From CPUA
Change Rejected
Messenger has received an invalid ground
fault enable or disable setting from CPU A
and has rejected the value
This event is recorded by CPU B based on
status information sent to the Messenger by
CPU A. The Sequence of Events for CPU A
should have an “Invalid Setting GF Change
Rejected” or “Invalid Setting GF Pickup
Change Rejected” event. See the description
of those events for details.
Invalid Setting GF From CPUB
Change Rejected
Messenger has received an invalid ground
fault enable or disable setting from CPU B
and has rejected the value
This event is recorded by CPU A based on
status information sent to the Messenger by
CPU B. The Sequence of Events for CPU B
should have an “Invalid Setting GF Change
Rejected” or “Invalid Setting GF Pickup
Change Rejected” event. See the description
of those events for details.
Note Messngr Ignored Invalid
Command CPUA
Messenger has received an invalid command
from CPU A and will ignore it
Contact GE Post Sales Service (see
).
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips