Alarms and events description and system troubleshooting guide
259
A
Attention Messngr Synch 
Disabld Bad Freq CPUB
Messenger has received an invalid system 
frequency from CPU B and will not be able to 
synchronize from it
Contact GE Post Sales Service (see
).
Invalid Setting IOC Mult CPUA 
Chng Rejected
Messenger has received an invalid IOC 
pickup setting from CPU A and has rejected 
the value
This event is recorded by CPU B based on 
status information sent to the Messenger by 
CPU A. The Sequence of Events for CPU A 
should have an “Invalid Setting IOC Change 
Rejected” or “Invalid Setting IOC Pickup 
Change Rejected” event. See the description 
of those events for details.
Invalid Setting IOC Mult CPUB 
Chng Rejected
Messenger has received an invalid IOC 
pickup setting from CPU B and has rejected 
the value
This event is recorded by CPU A based on 
status information sent to the Messenger by 
CPU B. The Sequence of Events for CPU B 
should have an “Invalid Setting IOC Change 
Rejected” or “Invalid Setting IOC Pickup 
Change Rejected” event. See the description 
of those events for details.
Invalid Setting ST From CPUA 
Change Rejected
Messenger has received an invalid short time 
enable or disable setting from CPU A and has 
rejected the value
This event is recorded by CPU B based on 
status information sent to the Messenger by 
CPU A. The Sequence of Events for CPU A 
should have an “Invalid Setting ST Change 
Rejected” or “Invalid Setting ST Pickup 
Change Rejected” event. See the description 
of those events for details.
Invalid Setting ST From CPUB 
Change Rejected
Messenger has received an invalid short time 
enable or disable setting from CPU B and has 
rejected the value
This event is recorded by CPU A based on 
status information sent to the Messenger by 
CPU B. The Sequence of Events for CPU B 
should have an “Invalid Setting ST Change 
Rejected” or “Invalid Setting ST Pickup 
Change Rejected” event. See the description 
of those events for details.
Invalid Setting GF From CPUA 
Change Rejected
Messenger has received an invalid ground 
fault enable or disable setting from CPU A 
and has rejected the value
This event is recorded by CPU B based on 
status information sent to the Messenger by 
CPU A. The Sequence of Events for CPU A 
should have an “Invalid Setting GF Change 
Rejected” or “Invalid Setting GF Pickup 
Change Rejected” event. See the description 
of those events for details.
Invalid Setting GF From CPUB 
Change Rejected
Messenger has received an invalid ground 
fault enable or disable setting from CPU B 
and has rejected the value
This event is recorded by CPU A based on 
status information sent to the Messenger by 
CPU B. The Sequence of Events for CPU B 
should have an “Invalid Setting GF Change 
Rejected” or “Invalid Setting GF Pickup 
Change Rejected” event. See the description 
of those events for details.
Note Messngr Ignored Invalid 
Command CPUA
Messenger has received an invalid command 
from CPU A and will ignore it
Contact GE Post Sales Service (see
).
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips