Specifications, 1 environmental, 2 type tests – GE Industrial Solutions Entellisys 4.0 System User Manual User Manual
Page 27: 2 specifications, 1 environmental 2.2 type tests, 2specifications

Environmental
27
2
2
Specifications
2.1 Environmental
Storage/shipping temperatures
–40 to 85° C
Operating temperatures
0 to 40° C ambient, indoor use
Humidity
5% to 95%, non-condensing, indoor use
2.2 Type tests
Tests are split into two categories:
•
EntelliGuard Messenger Tests – the primary protection control element
•
Entellisys System Tests – the complete system
Table 2-1 Type tests
Type
Name
EntelliGuard Messenger
Tests
Entellisys System Tests
EMC/Transient
Harmonic Currents
IEC60947-2 sec.F.4.1.2
EMC/Transient
Current Dips and
Interruptions
IEC60947-2 sec. F.4.2
EMC/Transient
Fast Transient Burst
IEC61000-4-4
ANSI C37.90.1
ANSI C37.90.1
ANSI C62.41
IEC61000-4-4
EMC/Transient
Voltage/Current Surge
Immunity
IEC61000-4-5
IE255-22-5
ANSI C62.41
IEC61000-4-4
EMC/Transient
Electrostatic Discharge
Immunity
IEC60947-2 sec. F.4.3
IEC60255-6
EN61000-4-2
EMC/Transient
1MHz Oscillatory SWC
IEC 60255-22-1
ANSI C37.90.1
ANSI C37.90.1
EM emission
Conducted
FCC part 15, subpart B, Class A
EM emission
Radiated
FCC part 15, subpart B, Class A
RFI
Electromagnetic Field
Immunity
IEC60947-2 sec. F.4.4