Alarms and events description and system troubleshooting guide
269
A
Breaker Close Command 
Rejected Breaker Locked Out
Breaker is locked out, so CPU has rejected 
the close command
•
If breaker has a manual lockout, verify 
that the lockout has been reset.
•
If the breaker has a network interlock, the 
control logic is likely causing the breaker 
to reject the close command.
•
Contact GE Post Sales Service (see
).
Attention IO Card Detection 
Mismatch Found 0 of 1
CPU expected 1 discrete I/O card, but 
detected none
Contact GE Post Sales Service (see
).
Attention IO Card Detection 
Mismatch Found 0 of 2
CPU expected 2 discrete I/O cards, but 
detected none
Contact GE Post Sales Service (see
).
Attention IO Card Detection 
Mismatch Found 1 of 0
CPU expected no discrete I/O cards, but 
detected 1
Contact GE Post Sales Service (see
).
Attention IO Card Detection 
Mismatch Found 1 of 2
CPU expected 2 discrete I/O cards, but 
detected 1
Contact GE Post Sales Service (see
).
Attention IO Card Detection 
Mismatch Found 2 of 0
CPU expected no discrete I/O cards, but 
detected 2
Contact GE Post Sales Service (see
).
Attention IO Card Detection 
Mismatch Found 2 of 1
CPU expected 1 discrete I/O card, but 
detected 2
Contact GE Post Sales Service (see
).
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips