GE Industrial Solutions Entellisys 4.0 System User Manual User Manual
Page 248

Alarms and events
248
A
Voltage Below Phase Loss Alarm
Blocking Voltage
The voltages on all three phases have
dropped below the alarm only phase loss
blocking voltage threshold.
Voltage Above Phase Loss
Alarm Blocking Voltage
The voltage on at least one of the three
phases has exceeded the alarm only phase
loss blocking voltage threshold.
Pickup Phase Loss
Phase loss relay has entered pickup
Breaker Trip Phase Loss
Phase loss relay has operated
Dropout Phase Loss
Phase loss relay has dropped out of pickup
Voltage Below Phase Loss
Blocking Voltage
The voltages on all three phases have
dropped below the phase loss blocking
voltage threshold.
Voltage Above Phase Loss
Blocking Voltage
The voltage on at least one of the three
phases has exceeded the phase loss blocking
voltage threshold.
Relays - High Current
Alarm Pickup High Current
High current relay has entered pickup
Alarm High Current
High current relay has operated
Alarm Dropout High Current
High current relay has dropped out of pickup
Relays - Frequency and Reverse Power
Alarm Pickup Reverse Power
Alarm only reverse power relay has entered
pickup
Alarm Reverse Power
Alarm only reverse power relay has operated
Alarm Dropout Reverse Power
Alarm only reverse power relay has dropped
out of pickup
Pickup Reverse Power
Reverse power relay has entered pickup
Breaker Trip Reverse Power
Reverse power relay has operated
Dropout Reverse Power
Reverse power relay has dropped out of
pickup
Alarm Pickup Underfrequency
Alarm only underfrequency relay has entered
pickup
Alarm Underfrequency
Alarm only underfrequency relay has
operated
Alarm Dropout Underfrequency Alarm only underfrequency relay has
dropped out of pickup
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips