GE Industrial Solutions Entellisys 4.0 System User Manual User Manual
Page 248

Alarms and events
248
A
Voltage Below Phase Loss Alarm 
Blocking Voltage
The voltages on all three phases have 
dropped below the alarm only phase loss 
blocking voltage threshold.
Voltage Above Phase Loss 
Alarm Blocking Voltage
The voltage on at least one of the three 
phases has exceeded the alarm only phase 
loss blocking voltage threshold.
Pickup Phase Loss
Phase loss relay has entered pickup
Breaker Trip Phase Loss
Phase loss relay has operated
Dropout Phase Loss
Phase loss relay has dropped out of pickup
Voltage Below Phase Loss 
Blocking Voltage
The voltages on all three phases have 
dropped below the phase loss blocking 
voltage threshold.
Voltage Above Phase Loss 
Blocking Voltage
The voltage on at least one of the three 
phases has exceeded the phase loss blocking 
voltage threshold.
Relays - High Current
Alarm Pickup High Current
High current relay has entered pickup
Alarm High Current
High current relay has operated
Alarm Dropout High Current
High current relay has dropped out of pickup
Relays - Frequency and Reverse Power
Alarm Pickup Reverse Power
Alarm only reverse power relay has entered 
pickup
Alarm Reverse Power
Alarm only reverse power relay has operated
Alarm Dropout Reverse Power
Alarm only reverse power relay has dropped 
out of pickup
Pickup Reverse Power
Reverse power relay has entered pickup
Breaker Trip Reverse Power
Reverse power relay has operated
Dropout Reverse Power
Reverse power relay has dropped out of 
pickup
Alarm Pickup Underfrequency
Alarm only underfrequency relay has entered 
pickup
Alarm Underfrequency
Alarm only underfrequency relay has 
operated
Alarm Dropout Underfrequency Alarm only underfrequency relay has
dropped out of pickup
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips
