Introduction to FlexLogic
171
11
Table 11-2 describes all available operands available for all entellisys relays and are listed 
alphabetically by operand type.
NOTE: While all relay elements and operands are available in FlexLogic, relays that are 
optionable will not function unless properly optioned and configured.
Table 11-2 Entellisys FlexLogic operands
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
ELEMENT:
Breaker Control
BREAKER 1 OPENED
BREAKER 1 CLOSED
BREAKER 1 LOCKED OUT
BREAKER 1 CLOSED SPRING CHRGD
BREAKER 1 PRIMARY CONNECTED
BREAKER 1 PRIMARY DISCONNECTED
BREAKER 1 SECONDARY CONNECTED
Breaker 1 open
Breaker 1 closed
Breaker 1 locked out
Breaker 1 closing spring charged
Breaker 1 primary connected
Breaker 1 primary disconnected
Breaker 1 secondary connected
BREAKER 1 AVAILABLE
TRUE when both the primary and secondary 
disconnects are connected.
BREAKER 1 READY
TRUE when the breaker is closed and both 
primary and secondary are connected.
BREAKER 1 OPEN FAILED
TRUE when open operation failed for the 
breaker. The result is set until breaker 
opened. Applies to all open and trip 
commands: shunt trip open, shunt trip, flux 
shifter open, flux shifter trip.
BREAKER 1 CLOSE FAILED
TRUE when close operation failed for the 
breaker. The result is set until breaker 
closed.
BREAKER 1 FAULT
TRUE when LT, ST, GF, multipoint relays or 
single point relays operated on a fault. The 
result is set until the fault is cleared. Breaker 
x Fault is returned to false when the breaker 
is opened or open time-out (550ms).
BREAKER 2…30
Same set of operands as shown for 
BREAKER 1