Sequence of events, fault reports and waveform capture records
140
9
•
Events Color - Changes the default colors of event categories. The color of the event text
helps the user quickly identify specific types of events. To see the list of events and the
categories, see
.
Figure 9-5 Event Category Colors
The categories are defined as follows:
Attention - An Entellisys issue that may potentially cause a future problem that should be
addressed at the next service interval
Caution - An Entellisys issue that is causing an immediate problem and should be
addressed immediately
Trip - A relay operation that tripped a breaker
Alarm - A power system event that caused a relay to exceed the alarm setting thresholds
Others - Conditions that occur during normal operation that are informative in nature
•
Protect/Overwrite – In Protect mode, the event logger stops recording events when the
maximum size of the daily log is reached. In Overwrite mode, the oldest events are
overwritten on a FIFO basis.
•
Event Log Size – Specifies the maximum size of the daily log.
•
Maximum Fault Reports – Specifies the point at which the HMI should stop automatically
retrieving Fault Reports in a given day.
•
Retention Days – Specifies the number of days to retain event records before they should be
automatically deleted to conserve disk space.