Chapter 6 – B&B Electronics ADAM-5000_TCP - Manual User Manual
Page 294

Planning Your Application Program
$aaSiCjAhU(data)
Name
Set Alarm Limit
Chapter 6
Description
Set the High/Low alarm limit value for the specified
input channel of a specified ADAM-5000/TCP sys-
tem.
Syntax $aaSiCjAhU(data)(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system. SiCj identifies the desired slot i and the
desired chan- nel j.
AhU is the Set Alarm Limit command.
h indicates alarm type and can have the value H =
High alarm, L = Low alarm
(data) represents the desired alarm limit setting. The
value is from 0 to 4294967295. Be aware that (data)
has 10 characters.
(cr) represents terminating character, carriage return
(0Dh)
Response !aa(cr)
if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.
ADAM-5000/TCP User’s Manual
6-181