Planning Your Application Program

$aaSiCjAhU(data)

Name

Set Alarm Limit

Chapter 6





Description

Set the High/Low alarm limit value for the specified

input channel of a specified ADAM-5000/TCP sys-
tem.

Syntax $aaSiCjAhU(data)(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system. SiCj identifies the desired slot i and the
desired chan- nel j.

AhU is the Set Alarm Limit command.

h indicates alarm type and can have the value H =
High alarm, L = Low alarm

(data) represents the desired alarm limit setting. The
value is from 0 to 4294967295. Be aware that (data)
has 10 characters.

(cr) represents terminating character, carriage return
(0Dh)

Response !aa(cr)

if the command was valid There is no

response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.

! delimiter character indicating a valid command was
received.

aa represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.



ADAM-5000/TCP User’s Manual