background image

Planning Your Application Program

Chapter 6

Example

command: $01S0C1AHU+080.00(cr)

response: !01(cr)

Channel 1 of slot 0 in the ADAM-5000/TCP system
at address 01h is configured to accept type-T ther-
mocouple input. The command will set its High alarm
limit to +80°C.

The system confirms the command has
been re- ceived.

Note: An analog input module requires a maximum of 2 seconds after

it receives a Set Alarm Limit command to let the settings take
effect. During this interval, the module cannot be addressed to
perform any other actions.































ADAM-5000/TCP User’s Manual































6-103