Chapter 6 – B&B Electronics ADAM-5000_TCP - Manual User Manual
Page 284

Planning Your Application Program
$aaSiCjAhEs
Name
Set Alarm Disable/Latch
Chapter 6
Description
The addressed counter module is instructed to set
alarm disable or latch.
Syntax $aaSiCjAhEs(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system. SiCj identifies the desired slot i and the
desired chan- nel j. AhEs is the command for setting
Alarm Disable/Latch Mode command.
h indicates alarm type and can have the value H =
High alarm, L = Low alarm
s indicates alarm enable/disable and can have the
value D = Disable, E=Enable
(cr) represents terminating character, carriage return
(0Dh)
Response !aa(cr)
if the command was valid There is no
response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.
(cr) represents terminating character, carriage return
(0Dh)
ADAM-5000/TCP User’s Manual
6-171