beautypg.com

Chapter 6 – B&B Electronics ADAM-5000_TCP - Manual User Manual

Page 284

background image

Planning Your Application Program

$aaSiCjAhEs

Name

Set Alarm Disable/Latch

Chapter 6





Description

The addressed counter module is instructed to set

alarm disable or latch.

Syntax $aaSiCjAhEs(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system. SiCj identifies the desired slot i and the
desired chan- nel j. AhEs is the command for setting
Alarm Disable/Latch Mode command.

h indicates alarm type and can have the value H =
High alarm, L = Low alarm

s indicates alarm enable/disable and can have the
value D = Disable, E=Enable

(cr) represents terminating character, carriage return
(0Dh)

Response !aa(cr)

if the command was valid There is no

response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.

! delimiter character indicating a valid command was
received.

aa represents the 2-character hexadecimal Modbus
network address of the corresponding ADAM-5000/
TCP system.

(cr) represents terminating character, carriage return
(0Dh)



ADAM-5000/TCP User’s Manual


6-171