B&B Electronics ADAM-5000_TCP - Manual User Manual
Page 138

Planning Your Application Program
#aaSiCj
Name
Specified Analog Data In
Chapter 6
Description
Returns the input value of a specified channel for a
specified analog input module of a specified system
in engineering unit only.
Syntax #aaSiCj(cr)
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of the ADAM-5000/
TCP system you want to interrogate.
Si identifies the I/O slot you want to interrogate.
Cj identifies the channel you want to read.
(cr) is the terminating character, carriage return (0Dh)
Response
>(data) if the command is valid.
?aa(cr) if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exist.
> is a delimiter character indicating a valid command
was received.
? delimiter character indicating the command was
invalid.
(data) is the input value in engineering units of the
specified channel for a specified analog input mod-
ule of the specified system. If (data) = “ “, it means
the channel is invalid.
(cr) is the terminating character, carriage return (0Dh)
ADAM-5000/TCP User’s Manual
6-71