Planning Your Application Program

$aaSiCj5

Name

Read counter Start/Stop

Chapter 6





Description

Requests the addressed counter/frequency module

to indicate whether counters are active.

Syntax $aaSiCj5(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of the ADAM-5000/
TCP system.

SiCj identifies the I/O slot i and the channel j of the
module you want to set.

5 is the command for reading counter Start/Stop.

(cr) is the terminating character, carriage return (0Dh)

Response !aas

(cr)

if the command is valid.

?aa (cr) if an invalid operation was entered. There
is no response if the module detects a syntax error
or communication error or if the specified ad- dress
does not exists.

! delimiter character indicating a valid command was
received.

? delimiter character indicating the command was
invalid.

aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.

s represents start/stop command.

s=0 indicate stop counter. s=1

indicate start counter.

(cr) is the terminating character, carriage return (0Dh)