beautypg.com

B&B Electronics ADAM-5000_TCP - Manual User Manual

Page 209

background image

Chapter 6


Planning Your Application Program

(cr) is the terminating character, carriage return (0Dh)

Example

command: $01S2C16(cr)

response: !0103.000(cr) The command tells
channel 1 of the analog output module in slot 2 of
the ADAM-5000/TCP system at address 01h to
return the last output value it received from an
Analog Data Out command, or its start-up output
current /voltage. The analog output module returns
the value 3.000 mA (this assumes that the module
was configured for the range 0-20 mA).


































6-140

ADAM-5000/TCP User’s Manual