beautypg.com

B&B Electronics ADAM-5000_TCP - Manual User Manual

Page 132

background image

Planning Your Application Program

Chapter 6

Response !aa(cr)

if the command is valid.

?aa(cr) if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exist.

! delimiter character indicating a valid command was
received.

? delimiter character indicating the command was in-
valid.

aa (range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.

(cr) is the terminating character, carriage return (0Dh)

Example

command: $01S3A0000(cr)

response: !01(cr)

The analog input module in slot 3 of the ADAM-
5000/TCP system at address 01h is configured to an
input range ±15mV, engineering units data format, and
integration time 50ms (60Hz). The response indicates
that the command has been received.

Note:

An analog input module requires a maximum of 7 seconds to

perform auto calibration and ranging after it is reconfigured.
During this time span, the module cannot be addressed to per-
form any other actions.
















ADAM-5000/TCP User’s Manual