Chapter 6 – B&B Electronics ADAM-5000_TCP - Manual User Manual
Page 283

Chapter 6
Planning Your Application Program
@aaSiCjG
Name
Read Initial Counter
Description
Read initial counter value of specified module.
Syntax @aaSiCjG(cr)
@ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of the ADAM-5000/TCP system.
SiCj identifies the I/O slot i and the channel j for the
module you want to return a prior value. G is the last
value readback command.
(cr) is the terminating character, carriage return (0Dh)
Response !aa(data)(cr)
if the command is valid.
?aa(cr) if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was in-
valid.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.
(data) is initial value from 0 to 4294967295.Be aware
that (data) has 10 characters.
(cr) is the terminating character, carriage return (0Dh)
Example
command: @01S3C2G(cr)
response: !010000004369(cr)
The channel 2 of ADAM-5080 in slot 3 in ADAM-
5000/TCP system at address 01h is instructed to re-
turn counter initial value. The initial counter value is
4369.
}