Planning Your Application Program

ADAM-5081 Counter/Frequency Command Set

Command Syntax

Command Name

Description


$aaT

Read Module Name

Returns the module
name from a specified
ADAM-5000 system.

$aaF

Read Firmware

Version

Returns the firmware
version code from a
specified ADAM-5000
system

$aaSiArrff

Set Configuration

Set slot index and

Counter mode

$aaSiB

Read Configuration

The command requests
the Configuration of slot


#aaSi

Read All Channel

Counter (Frequency)
Data

Returns the input value of

all channels for the

specified input module

for a specified system in

engineering unit only.


#aaSiCj


Read One Channel
Counter (Frequency)
Data

The command will return

the input value from one
of the four channels of a
specified module.

$aaSiØ(data)

Set Digital filter Scale

Set the filter seconds to

start to measure the input

signal.

$aaSiØ

Read Digital filter

scale

Read the filter seconds
to start to measure the
input signal

$aaSiCj5s

Set Counter

Start/Stop

Request the addressed
counter/frequency
module to start or

stop the counting.



6-148