beautypg.com

B&B Electronics ADAM-5000_TCP - Manual User Manual

Page 230

background image

Planning Your Application Program

Chapter 6

$aaSi0(data)

Name

Set Digital filter Scale

Description

Set the filter seconds to start to measure the input

signal.

Syntax $aaSi0(data)(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadeci-
mal address of the ADAM-5000/TCP system which
is to be calibrate.

Si identifies the specified slot.

0 is the command for setting digital filter scale.

(data) represents filter seconds from 8µs~65000 µs.
Be aware that (data) has 5 characters.

(cr) is the terminating character, carriage return (0Dh)

Response !aa(cr)

if the command is valid.

?aa(cr) if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exists.

! delimiter character indicating a valid command was
received.

? delimiter character indicating the command was in-
valid.

aa (range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.

(cr) is the terminating character, carriage return (0Dh)

Example

command: $01S3000765(cr)

response: !01(cr)

The ADAM-5080 in slot 3 of the ADAM-5000/TCP
system at address 01h needs 765m seconds to start
to measure the input.





ADAM-5000/TCP User’s Manual





6-159