beautypg.com

B&B Electronics ADAM-5000_TCP - Manual User Manual

Page 286

background image

Planning Your Application Program

$aaSiCjAh

Name

Read Alarm Disable/Latch

Chapter 6





Description

Return the alarm mode for the specified channel.

Syntax $aaSiCjAh(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system. SiCj identifies the desired slot i and the
desired chan- nel j.

A is the Read Alarm Mode command.

h indicates alarm type and can have the value H =
High alarm, L = Low alarm

(cr) represents terminating character, carriage return
(0Dh)

Response !aap(cr)

if the command was valid There is no

response if the system detects a syntax error or
communication error or if the specified ad- dress
does not exist.

! delimiter character indicating a valid command was
received.

aa represents the 2-character hexadecimal Modbus
address of the corresponding ADAM-5000/TCP sys-
tem.

p indicates alarm mode.

p=D, if alarm is Disable.

P=L, if alarm is Latch.

(cr) represents terminating character, carriage return
(0Dh)


ADAM-5000/TCP User’s Manual


6-173