Chapter 6





Planning Your Application Program

mal Modbus

network address of an ADAM-5000/ TCP system.

(cr) is the terminating character, carriage return (0Dh).

Example

command: %01000A40(cr)

response: !01(cr)

The ADAM-5000/TCP system with address 01h is
configured to a baud rate of 115.2 Kbps and with
checksum generation or validation.

The response indicates that the command was re-
ceived. Wait 7 seconds to let the new configuration
setting take effect before issuing a new command to
the system.

Note:

All configuration parameters can be changed dynami-

cally, except checksum and baud rate parameters.
They can only be altered when the INIT* terminal is
grounded.

Baud Rate Code

Baud Rate

03h

1200 bps

04h

2400 bps

05h

4800 bps

06h

9600 bps

07h

19.2 Kbps

08h

38.4 Kbps

09h

57.6 Kbps

0Ah

115.2 Kbps

Table 6-3 Baud rate codes