Planning Your Application Program

$aaSiCj6

Name

Clear Counter

Chapter 6





Description

Clear the counters of the specified counter/frequency

module

Syntax $aaSiCj6(cr)

$ is a delimiter character.

aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of the ADAM-5000/
TCP system. SiCj identifies the I/O slot i and the
channel j for the module you want to return a prior
value.

6 is the command for clearing counter.

(cr) is the terminating character, carriage return (0Dh)

Response !aa(cr)

if the command is valid.

?aa(cr) if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exist.

! delimiter character indicating a valid command was
received.

? delimiter character indicating the command was in-
valid.

aa (range 00-FF) represents the 2-character hexadeci-
mal Modbus network address of an ADAM-5000/
TCP system.

(cr) is the terminating character, carriage return (0Dh)







ADAM-5000/TCP User’s Manual