B&B Electronics ADAM-5000_TCP - Manual User Manual
Page 231

Chapter 6
Planning Your Application Program
$aaSi0
Name
Read Digital filter scale
Description
Read the filter seconds to start to measure the input
signal.
Syntax $aaSi0(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of the ADAM-5000/TCP system which
is to be calibrate.
Si identifies the I/O slot which is to be accessed.
0 is the command for reading digital filter scale.
(cr) is the terminating character, carriage return (0Dh)
Response !aa(data)(cr)
if the command is valid.
?aa(cr) if an invalid operation was entered. There is
no response if the module detects a syntax error or
communication error or if the specified ad- dress
does not exists.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was in-
valid.
aa (range 00-FF) represents the 2-character hexadeci-
mal address of an ADAM-5000/TCP system.
(data) represents filter seconds from 8 µs~65000 µs.
Be aware that (data) has 5 characters.
(cr) is the terminating character, carriage return (0Dh)
Example
command: $01S30(cr)
response: !0100765(cr) The command requests the
ADAM-5080 in slot 3 of the ADAM-5000/TCP
system at address 01h to read the filter seconds. The
module responds with 765m seconds.
6-160
ADAM-5000/TCP User’s Manual