beautypg.com

Error count registers – Rainbow Electronics DS21458 User Manual

Page 85

background image

DS21455/DS21458 Quad T1/E1/J1 Transceivers

85 of 270

15. ERROR COUNT REGISTERS

The DS21455/DS21458 contain four counters that are used to accumulate line coding errors, path errors,
and synchronization errors. Counter update options include one second boundaries, 42ms (T1 mode
only), 62ms (E1 mode only) or manually. See Error Counter Configuration Register (ERCNT). When
updated automatically, the user can use the interrupt from the timer to determine when to read these
registers. All four counters will saturate at their respective maximum counts and they will not rollover
(Note: Only the line-code violation count register has the potential to overflow but the bit error would
have to exceed 10E-2 before this would occur).



Register Name:

ERCNT

Register Description:

Error Counter Configuration Register

Register Address:

41h


Bit

# 7 6 5 4 3 2 1 0

Name —

MECU

ECUS

EAMS

VCRFS

FSBE

MOSCRF

LCVCRF

Default

0 0 0 0 0 0 0 0


Bit 0/T1 Line Code Violation Count Register Function Select (LCVCRF).

0 = do not count excessive zeros
1 = count excessive zeros


Bit 1/Multiframe Out-of-Sync Count Register Function Select (MOSCRF).

0 = count errors in the framing bit position
1 = count the number of multiframes out of sync


Bit 2/PCVCR Fs-Bit Error Report Enable (FSBE).

0 = do not report bit errors in Fs-bit position; only Ft-bit position
1 = report bit errors in Fs-bit position as well as Ft-bit position


Bit 3/E1 Line Code Violation Count Register Function Select (VCRFS).

0 = count Bipolar Violations (BPVs)
1 = count Code Violations (CVs)

Bit 4/Error Accumulation Mode Select (EAMS).

0 = ERCNT.5 determines accumulation time
1 = ERCNT.6 determines accumulation time


Bit 5/Error Counter Update Select (ECUS).

T1 Mode: 0 = Update error counters once a second

1 = Update error counters every 42ms (333 frames)

E1 Mode: 0 = Update error counters once a second

1 = Update error counters every 62.5ms (500 frames)


Bit 6/Manual Error Counter Update (MECU). When enabled by ERCNT.4, the changing of this bit from a zero to a one
allows the next clock cycle to load the error counter registers with the latest counts and reset the counters. The user must wait a
minimum of 1.5 RCLK clock periods before reading the error count registers to allow for proper update.

Bit 7/Unused, must be set to zero for proper operation.