Honeywell DCP552 Mark II User Manual

Page 184

background image

11-2

Item

Specifications

Input section

External switch

input section

Display and

setting section

Cold junction compensation system Internal or external compensation (at 0¡C) selectable
Scaling

Ð19999 to +20000U (Only linear input settable. Reverse scaling and optional decimal point position settable.)

Root extraction

Drop out 0.2 to 10.0%. DC current and DC voltage range settable.

PV equalizer

(linearization)

PV1: 9 brend lines (10 settings)

PV2: 9 brend lines (10 settings)

CP : 9 brend lines (10 settings)

Input bias

Ð1000 to +1000U variable

Digital filter

0.0 to 120.0s variable (0.0: Filter off)

Input count

16 point

Open terminal voltage

8.5V

±

0.5V during common terminal ((12) and (40) terminals) and every input

terminal (under operating conditions)

Terminal current in case of short circuit Current to run every terminal is about 6mA (under operating conditions)
Allowable contact resistance

(no-voltage contact)

On decision: Lower than 250½ (under operating conditions)

Off decision: Higher than 100 k½ (under operating conditions)

Allowable residual current

(open collector ON)

Lower than 2V (under operating conditions)

Leakage current

(open collector OFF)

Lower than 0.1mA (under operating conditions)

Allocation (fixed)

RUN, HOLD, RESET, ADV, program number, CH1 and CH2 operation canceled

Allocation (variable)

RAMP-E, FAST, AT, AUTO/MANUAL, G.SOAK reset, auto load, O

2

sensor

check

Display panel 1

Digital 5 places, 7 segments, green

Indicates PV and other data in basic display status, indicates an item code in parameter setting status.

Display panel 2

Digital 5 places, 7 segments, orange

Indicates SP, output %, and other data in basic display status, indicates a set point of item in parameter setting status.

On detection Min. hold time

0.2s (program number is 0.4s)

Input sampling cycle

0.1s

Segment number display

Digital 2 places, 7 segments, green

Indicates a segment number in basic display status, indicates a item number in parameter setting status.

Indicates an alarm code number when an alarm occurs.

Program number display

Digital 2 places, 7 segments, green

Indicates a program number in basic display status.

Message display panel

Indicates output graph, deviation graph, event status, program tag, and other data in basic display status,

Displays reference messages during parameter and program settings.

Indicates operations and operation results during memory card operation.

Profile display

7 plane light-emitting LED, orange

Indicates the rising, soaking, and falling tendencies of program pattern.

Each status display

22 plane light-emitting LED

Mode

: RUN, HLD, MAN, PRG (green)

Display contents: PV, SP, OUT, TM, CYC, SYN, DEV (green), EG1, EG2 (red)

Battery voltage : BAT (red) (flickers when the battery voltage has dropped.)

Status

: AT (green)

Status displays

18 rubber keys

Loader connection port

1 (Using exclusive connection cable, stereo pin jack)

Connectable output type

No-voltage contact (relay contact), and open collector (sink current toward 0V)

Chapter 11. SPECIFICATIONS