Honeywell DCP552 Mark II User Manual
Page 184
11-2
Item
Specifications
Input section
External switch
input section
Display and
setting section
Cold junction compensation system Internal or external compensation (at 0¡C) selectable
Scaling
Ð19999 to +20000U (Only linear input settable. Reverse scaling and optional decimal point position settable.)
Root extraction
Drop out 0.2 to 10.0%. DC current and DC voltage range settable.
PV equalizer
(linearization)
PV1: 9 brend lines (10 settings)
PV2: 9 brend lines (10 settings)
CP : 9 brend lines (10 settings)
Input bias
Ð1000 to +1000U variable
Digital filter
0.0 to 120.0s variable (0.0: Filter off)
Input count
16 point
Open terminal voltage
8.5V
±
0.5V during common terminal ((12) and (40) terminals) and every input
terminal (under operating conditions)
Terminal current in case of short circuit Current to run every terminal is about 6mA (under operating conditions)
Allowable contact resistance
(no-voltage contact)
On decision: Lower than 250½ (under operating conditions)
Off decision: Higher than 100 k½ (under operating conditions)
Allowable residual current
(open collector ON)
Lower than 2V (under operating conditions)
Leakage current
(open collector OFF)
Lower than 0.1mA (under operating conditions)
Allocation (fixed)
RUN, HOLD, RESET, ADV, program number, CH1 and CH2 operation canceled
Allocation (variable)
RAMP-E, FAST, AT, AUTO/MANUAL, G.SOAK reset, auto load, O
2
sensor
check
Display panel 1
Digital 5 places, 7 segments, green
Indicates PV and other data in basic display status, indicates an item code in parameter setting status.
Display panel 2
Digital 5 places, 7 segments, orange
Indicates SP, output %, and other data in basic display status, indicates a set point of item in parameter setting status.
On detection Min. hold time
0.2s (program number is 0.4s)
Input sampling cycle
0.1s
Segment number display
Digital 2 places, 7 segments, green
Indicates a segment number in basic display status, indicates a item number in parameter setting status.
Indicates an alarm code number when an alarm occurs.
Program number display
Digital 2 places, 7 segments, green
Indicates a program number in basic display status.
Message display panel
Indicates output graph, deviation graph, event status, program tag, and other data in basic display status,
Displays reference messages during parameter and program settings.
Indicates operations and operation results during memory card operation.
Profile display
7 plane light-emitting LED, orange
Indicates the rising, soaking, and falling tendencies of program pattern.
Each status display
22 plane light-emitting LED
Mode
: RUN, HLD, MAN, PRG (green)
Display contents: PV, SP, OUT, TM, CYC, SYN, DEV (green), EG1, EG2 (red)
Battery voltage : BAT (red) (flickers when the battery voltage has dropped.)
Status
: AT (green)
Status displays
18 rubber keys
Loader connection port
1 (Using exclusive connection cable, stereo pin jack)
Connectable output type
No-voltage contact (relay contact), and open collector (sink current toward 0V)
Chapter 11. SPECIFICATIONS