Honeywell DCP552 Mark II User Manual
Page 176

10-5
●
Autotuning cannot be canceled with AT key
●
PID parameter setting state cannot be invoked with PID key
●
Event configuration setting state cannot be invoked with FUNC and PARA keys
●
Setup data setting state cannot be invoked with SETUP key
●
Fixed command control data setting state cannot be invoked with FUNC and PID keys
●
Program setting state cannot be invoked with FUNC and PROG keys
●
Program copy cannot be performed with
↑
and PROG keys
Cause
Measure
Set to be except READY mode.
Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys).
Program selected in READY mode is unset.
Select number ofa set program.
Fixed command control mode is on.
Set fixed command control data
ConSt
to 0.
Mode other than READY
Press DISP key to invoke normal display mode.
Program protected
Set variable parameter
PA02
to 0, 2 or 4.
Set to key lock.
Set variable parameter
PA01
to 0.
Cause
Measure
Normal display mode not on
Press DISP key to invoke normal display mode.
Set to fixed command control mode.
Set fixed command control data
ConSt
setting to 0.
Set to key lock.
Set variable parameter
PA01
to 0 or 1.
Cause
Measure
Normal display mode not on
Press DISP key to invoke normal display mode.
Mode other than READY
Set READY mode to execute RESEToperation (PROG +
RUN/HOLD keys).
Set to key lock.
Set variable parameter
PA01
to 0 or 1.
Cause
Measure
Normal display mode not on
Press DISP key to invoke normal display mode.
Mode other than READY
Set READY mode to execute RESEToperation (PROG +
RUN/HOLD keys).
Set to key lock.
Set variable parameter
PA01
to 0.
Cause
Measure
Normal display mode not on
Press DISP key to invoke normal display mode.
Set to key lock.
Set variable parameter
PA01
to 0 or 1.
Cause
Measure
Set to key lock.
Set variable parameter
PA01
between 0 to 2.
Chapter 10. TROUBLESHOOTING