Honeywell DCP552 Mark II User Manual
Page 135
7-36
■
Constant value control data (CH1) setting
■
Constant value control data (CH2) setting
0: Program run mode
1: Fixed command control mode
0
ConSt
1
Control mode
Within the range of setup
C69
to
C70
(SP limit)
0
SP
2
Setpoint
0.0 to 1000.0%
A setting of 0.0 turns on ON-OFF control
100.0
P
3
Proportional band
0 to 3600 sec
No integral operation when set to 0.
[Description:]
When
P
is set to 0, [----] is displayed and setting cannot
be performed.
0
I
4
Integral time
0 to 12600 sec
No integral operation when set to 0.
[Description:]
When
P
is set to 0.0, [----] is displayed and setting
cannot be performed.
0
d
5
Derivative time
0.0 to 100%
[Description:]
When
P
is set to 0.0, [----] is displayed and setting cannot
be performed. When
I
is not equal to 0, [----] is displayed
and setting cannot be performed.
50.0
rE
6
Manual reset
-5.0 to upper limit %
0.0
oL
7
Manipulated variable lower limit
Lower limit to +105%
100.0
oH
8
Manipulated variable upper limit
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
0: Program run mode
1: Fixed command control mode
0
ConSt
1
Control mode
Within the range of setup
C66
to
C67
(SP limit)
0
SP
2
Setpoint
0.0 to 1000.0%
A setting of 0.0 turns on ON-OFF control
100.0
P
3
Proportional band
0 to 3600sec
No integral operation when set to 0.
[Description:]
When
P
is set to 0.0, Т-----У is displayed and setting
cannot be performed.
0
I
4
Integral time
0 to 1200 sec
No integral operation when set to 0.
[Description:]
When
P
is set to 0.0, Т-----У is displayed and setting
cannot be performed.
0
d
5
Derivative time
0.0 to 100.0%
[Description:]
When
P
is set to 0.0, Т-----У is displayed and setting
cannot be performed.When
I
is not equal to 0, Т-----У is
displayed and setting cannot be performed.
50.0
rE
6
Manual reset
-5.0 to upper limit %
0.0
oL
7
Manipulated variable lower limit
Lower limit to +105%
100.0
oH
8
Manipulated variable upper limit
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
Chapter 7. PARAMETER SETUP