Setting event items handling precautions – Honeywell DCP552 Mark II User Manual
Page 142

8-7
■
Setting event items
Handling Precautions
Events assigned to the selected channel can be displayed.
Note that when setup data C57 is set to 1, event items on the programming
map are skipped and not displayed.
●
When the event is a PV event
(1) In the set value display state, move to the segement event item to be set on the
programming map.
(2) Press the
ENTER key
to make display panel 1 flash (registration of first
setting).
(3) Use the
↑, ↓, ←, and →
keys
to make the first setting – setting the event
operating point.
Setting range : OFF –19999 to +20000 SPU
: OFF 0 to 20000 SPU (for absolute value deviation events)
: OFF –5.0 to +105.0% (for MV events)
(4) Press the
ENTER key
to stop the flashing on display panel 1. (Pressing the
FUNC
and
CLR keys
causes display panel 1 to return to unset state “-----”
and the flashing stops.)
●
Display (PV events)
Unset values are indicated as “ ----- ”.
NOTE
A PV event setting consists of a setting (including OFF) and a subfunction. A
subfunction cannot be used when a setting has not been made “ ----- ”.
PROG
SEG
PROFILE
Program
number
Segment
number
Set operating point
Pattern trend
Event number
Event type
Chapter 8. PROGRAM SETUP