Honeywell DCP552 Mark II User Manual
Page 178

10-7
●
PID group, output limiter group number items cannot be displayed with
↑
and
↓
keys
●
G.SOAK items, PV shift items and repeat items cannot be displayed with
↑
and
↓
keys
●
PV start items, cycle items and pattern link items cannot be displayed with
↑
and
↓
keys
●
Segment insertion and deletion cannot be confirmed with FUNC and ENTER keys
●
Program deletion cannot be confirmed with FUNC and ENTER keys during pattern item
registration
Cause
Measure
Program being set is running (in RUN,
HOLD, FAST, END, READY FAST).
Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys).
Cause
Measure
Set to memory protect.
Set variable parameter
PA02
to 0, 2 or 4.
Program being set is running (in RUN,
HOLD, FAST, END, READY FAST).
Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys).
Not set to pattern item on programming map. Move to the pattern item on the programming map.
This segment is not set on the programming
map.
Move to a set segment or set the segment.
Cause
Measure
Programming item display off
Set setup data
C60
to 0.
Cause
Measure
Programming item display off
Set setup data
C59
to 0.
Cause
Measure
Programming item display off
Set setup data
C58
to 0.
Chapter 10. TROUBLESHOOTING