7-14
*1:
Code event auxiliary setting 1 (number of output points) can be changed only in the READY mode.
*2:
Auxiliary setting 1 (number of output points) can be changed only in the READY mode.
Event type
24 to 63
65
66
64
Meaning
Message
Event off
OFF
Normal PV1 lower limit
operation PV1-L
Normal PV2 upper limit
operation PV2-H
Normal PV1 upper limit
operation PV1-H
Range of auxiliary
setting 1
Message
Unused
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Range of auxiliary
setting 2
Message
Unused
Operating point
Ð19999 to +20000 SPU
set point
Operating point
Ð19999 to +20000 SPU
set point
Operating point
Ð19999 to +20000 SPU
set point
Setting category
Operation category
Р
Р
Instrument type
PV type
Instrument type
PV type
Instrument type
PV type
Event type
67
69
70
68
Meaning
Message
Normal PV2 upper limit
operation PV2-L
PV lower limit
PV-L
Deviation upper limit
DEV-H
PV upper limit
PV-H
Range of auxiliary
setting 1
Message
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Range of auxiliary
setting 2
Message
Operating pointt
Ð19999 to +20000 SPU
set point
Operating point
Ð19999 to +20000 SPU
set point
Operating point
Ð19999 to +20000 SPU
set point
Operating point
Ð19999 to +20000 SPU
set point
Setting category
Operation category
Instrument type
PV type
Instrument type
PV type
Instrument type
PV type
Instrument type
PV type
Event type
20
22
23
21
Meaning
Message
SOAK absolute value deviation
lower limit S-A-DEV-L
SOAK absolute value deviation lower
limit with stanby S-A-DEV-L-W
Timer code event
T-CODE
SOAK absolute value deviation upper
limit with stanby S-A-DEV-H-W
Range of auxiliary
setting 1
Message
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Number of output points
1 to 8
*2
channels
Hysteresis
0 to 1000 SPU
hysteresis
Range of auxiliary
setting 2
Message
Unused
Unused
Unused
Unused
Setting category
Operation category
Segment type
PVtype
Segment type
PVtype
Segment type
Time type, code type
Segment type
PVtype
Event type
16
18
19
17
Meaning
Message
MV upper limit
MV-H
Code event
CODE
SOAK absolute value deviation
upper limit S-A-DEV-H
MV lower limit
MV-L
Range of auxiliary
setting 1
Message
Hysteresis
0.0 to 100.0%
hysteresis
Number of output points
1 to 8
*1
channels
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0.0 to 100.0%
hysteresis
Range of auxiliary
setting 2
Message
Unused
Unused
Unused
Unused
Setting category
Operation category
Segment type
PV type
Segment type
Code type
Segment type
PV type
Segment type
PV type
Chapter 7. PARAMETER SETUP