Chapter 9. MEMORY CARD OPERATIONS
■
Card battery alarm panel
When the voltage of the internal battery in a RAM card is too low, the data saved
on the disk may be corrupted. Loading corrupted data onto the
DCP552
will
cause maloperation. Do not use a card whose battery voltage is too low. If you
want to load the data anyway, select “
Ignore
” in this panel and press the
ENTER
key
. This displays the load menu. To return to the normal display mode, select
“
Quit
” or press the
ENTER key
or the
DISP key
.
■
Procedures for loading individual programs
This procedure loads single memory card files on the
DCP552
.
File number selection
L o a d P r o g r a m
0 1 P R O G 0 1 ?
Program number selection
ENTER key
L o a d 0 1 P R O G 0 1
D C P 0 1 ?
Program delete check
ENTER key
L o a d 0 1 P R O G 0 1
D C P 0 1 D e l e t e ?
Load check
ENTER key (Delete)
L o a d 0 1 P R O G 0 1
D C P 0 1 L O A D ?
Load complete
LOAD key
L o a d 0 1 P R O G 0 1
D C P 0 1 G o o d
ENTER key
↑
,
↓, ←
,
→
key
↑
,
↓, ←
,
→
key
(Displayed when there are
programs on the DCP552.)
↓
key (Not delete)
(Displays the tag to right side of the number.)
Card battery alarm screen
B a t t e r y A l a r m
Q u i t / I g n o r e ?
ENTER key
←, →
key
(The item indicated by the cursor can be selected.)
ÒQuitÓ returns you to the normal display mode.
ÒIgnoreÓ displays the load menu.