Procedures for loading event configuration data, Procedures for loading all parameters, Handling precautions – Honeywell DCP552 Mark II User Manual
Page 168

9-9
Chapter 9. MEMORY CARD OPERATIONS
■
Procedures for loading event configuration data
This procedure loads event configuration data on the memory card onto the
DCP552
.
■
Procedures for loading all parameters
This procedure loads all parameters on the memory card onto the
DCP552
.
Handling Precautions
The DCP552 Mark
II
and the old model, DCP552, differ in how some setup
data items are processed and the range of variable parameter PA15. Thus
the following changes have to be made when setup data, variable
parameters or all parameters saved on a DCP552 are loaded onto a
DCP552 Mark
II
.
• Setup data
: C21, C22, C45 to C50, C80, C90 to C97
• Variable parameters : PA15, PA25
Setup data and all parameters stored on a DCP552 Mark
II
cannot be
loaded onto a DCP552. (A loading attempt generates card error 16.)
Data delete check
D e l e t e O l d D a t a
L O A D ?
Load completed
LOAD key
A l l P a r a m e t e r s
L O A D G o o d
DISP key
Normal display mode
(Load operation is not performed.)
DISP key
Normal display mode
Data delete check
D e l e t e O l d D a t a
L O A D ?
Load completed
LOAD key
E V E N T D a t a
L O A D G o o d
DISP key
Normal display mode
(Load operation is not performed.)
DISP key
Normal display mode