Parameter setting related problems, Program setting related problems – Honeywell DCP552 Mark II User Manual
Page 177

10-6
●
General reset cannot be performed with FUNC, CLR and MESSAGE keys
■
Parameter setting related problems
●
Registration state cannot be invoked with ENTER key
■
Program setting related problems
●
Registration state cannot be invoked with ENTER key
●
Item changes cannot be made with
↑
and
↓
keys
●
SP values in program settings cannot be changed with
↑
and
↓
keys
●
Event items cannot be displayed with
↑
and
↓
keys
Cause
Measure
Event type is something other than segment
type.
Set the event type in the event configuration data to a value
between 1 and 23.
No event has been assigned to selected
channel.
Set correct value for setup data
C64
.
Programming item sets no display.
Set setup data
C57
to 0.
Cause
Measure
SP limit sets error value.
Set correct value for setup data
C66
,
C67
,
C69
and
C70
.
Cause
Measure
Not pattern item set.
Set SP and time data.
Cause
Measure
Set to memory protect.
Set variable parameter
PA02
to 0, 2 or 4.
Cause
Measure
Т-----У displayed in display panel 2
This item cannot be displayed or set. To change setting
connection item, it may be able to change or set.
Data displayed in display panel 2 cannot be changed. This item is display only.
Set to memory protect.
Set variable parameter
PA02
to 0.
Cause
Measure
Normal display mode not on
Press DISP key to invoke normal display mode.
Mode other than READY mode
Set READY mode to execute RESEToperation (PROG +
RUN/HOLD keys).
Set to MANUAL mode.
Set AUTO mode to execute AUTO operation (A/M key).
Set to memory protect.
Set variable parameter
PA02
to 0.
Set to key lock.
Set variable parameter
PA01
to 0.
Chapter 10. TROUBLESHOOTING