Honeywell N-ANN-RLY User Manual

N-ann-rly, Relay module, General

background image

DN-7107:A • 1/10/08 — Page 1 of 2

N-ANN-RLY

Relay Module

Annunciators

DN-7107:A • K-20

General

The N-ANN-RLY relay module provides 10 programmable

Form-C relays when used with a compatible FACP (Fire Alarm

Control Panel). The N-ANN-RLY module may be mounted

inside the FACP main circuit board chassis or in the battery

area of the enclosure using optional mounting bracket P/N:

ANN-MBRLY. Reference Installation Instructions document

#53318.
The N-ANN-RLY and the FACP communicate over a two-wire

serial interface employing the ANN-BUS communication for-

mat. An additional two wires are used for 24-volt DC power. A

single four-conductor unshielded cable may be used for both

power and data communications.
Up to eight ANN-BUS devices may be connected to the ANN-

BUS of each FACP.

Features

• N-ANN-RLY connects to the ANN-BUS terminal on the

FACP and requires minimal programming.

• Provides 10 programmable Form-C relays.
• Ten Form-C relays can be programmed for various func-

tions; Alarm, Trouble, Supervisory, AC Loss, Waterflow

Delay, Input Zones and Silenceable Alarm.

• Compatible with the FireWarden 50, SFP-5UD, RP-2001,

RP-2002 and SFP-10UD.

• May be powered by 24 VDC from the host FACP or by

remote power supply (requires 24 VDC).

• Up to eight ANN-BUS devices may be connected to the

ANN-BUS of each FACP.

• Listed to UL Standard 864, 9th Edition.

Specifications

• Maximum ANN-BUS Voltage: 24 VDC
• Maximum Current:

– Alarm: 75 mA Standby: 15 mA

• Ambient Temperature: 32ºF to 120ºF (0ºC to 49ºC)
• Relative Humidity: 93% ± 2% RH (noncondensing) at 32ºC

± 2ºC (90ºF ± 3ºF)

• For use indoors in a dry location
• Connections to FACP are power-limited and supervised.
• Relay Contact Ratings: 2 Amps @ 30VDC (Resistive) 0.5

Amps @ 30VAC (Resistive)

Agency Listings and Approvals

The listings and approvals below apply to the N-ANN-RLY. In

some cases, certain modules may not be listed by certain

approval agencies, or listing may be in process. Consult fac-

tory for latest listing status.

UL: S635

• CSFM:7165-0028:245; 7165-0028:246

MEA: 333-07-E

The ANN-BUS

POWERING THE DEVICES ON THE ANN-BUS FROM
AUXILIARY POWER SUPPLY

ANN-BUS devices can be powered by an auxiliary power sup-

ply when available panel power is exceeded. See FACP man-

ual for information.

ANN-BUS DEVICE ADDRESSING

Each ANN-BUS device requires a unique address (ID Num-

ber) in order to communicate with the FACP. A maximum of

eight devices can be connected to the FACP ANN-BUS com-

munication circuit. See the FACP manual for more information.

WIRE REQUIREMENTS

The N-ANN-RLY connects to the FACP ANN-BUS communica-

tions circuit. To determine the type of wire and the maximum

wiring distance, calculate the total worst case current draw for

all modules on a single 4-conductor bus. Use the table on the

following page to determine the maximum distance the mod-

ules can be located from the FACP. In general, the wire length

is limited by resistance, but for heavier wire gauges, capaci-

tance is the limiting factor. These cases are marked in the

chart with an asterisk (*). Maximum length can never be more

than 6,000 feet (1,800 m), regardless of gauge used.

Refer to the appropriate FACP manual for wiring details.

Ordering Information

• N-ANN-RLY Relay Module provides 10 programmable Form

C relays.

• ANN-MBRLY Optional mounting bracket.