Honeywell DCP552 Mark II User Manual
Page 145
8-10
●
When the event is a timer code event
(1) In the set value display state, move to the event item to be set for the segment
on the programming map.
(2) Press the
ENTER key
to make display panel 1 flash (registration of first
setting).
(3) Use the
↑, ↓, ←, and →
keys
to make the first setting (output code).
Setting range: 0 to 2
n
– 1
(n indicates the number of output points set in event
configuration 1 auxiliary setting 1.)
(4) Press the
ENTER key
to stop the flashing on display panel 1 and display
panel 2 starts flashing. (Start of second setting)
(Pressing the
FUNC
and
CLR keys
causes display panel 1 and 2 to return to
unset state “-----” and the flashing stops.)
(5) Use the
↑, ↓, ←, and →
keys
to make the second setting (time).
Setting range:
0:00 to 500:00, 0.0 to 3000.0
(Time units are selected using setup data
C64
to set Hour/min, Min/sec, 0.1
sec. Since a colon “
:
” cannot be displayed, the decimal point is used instead.)
(6) Press the
ENTER key
to stop the flashing on display panel 2.
(Pressing the
FUNC
and
CLR keys
causes display panel 1 and 2 to return to
unset state “-----” and the flashing stops.)
●
Display (Code event with a timer function)
Unset values are indicated as “-----”.
NOTE
Timer code events use one subfunction. A subfunction cannot be used when a
setting has not been made “-----”.
Events that follow the event number of a timer code event (number of output
points less 1) are skipped and not displayed.
PROG
SEG
PROFILE
Program
number
Segment
number
Event number and sub number
Event type and No. of outputs
Set time value
Output code setting
Pattern trend
Chapter 8. PROGRAM SETUP