Handling precautions – Honeywell DCP552 Mark II User Manual
Page 147
8-12
■
Setting PID groups and output limiter group number items
(1) In the set value display state, move to the PID group, output limiter group
number item to be set for the segment on the programming map.
(2) Press the
ENTER key
to make display panel 1 flash (registration of first
setting).
(3) Use the
↑, ↓, ←, and →
keys
to make the first setting (PID group number).
Setting range: ON-OFF, PID 0 to 9, PID A
(4) Press the
ENTER key
to stop the flashing on display panel 1 and display
panel 2 starts flashing. (Start of second setting)
(Pressing the
FUNC
and
CLR keys
causes display panel 1 and 2 to return to
unset state “
Pld 0/otL 0
” and the flashing stops.)
(5) Use the
↑, ↓, ←, and →
keys
to make the second setting (output limiter
group number).
Setting range: 0 to 9
(6) Press the
ENTER key
to stop the flashing on display panel 2.
(Pressing the
FUNC
and
CLR keys
causes display panel 2 to return to unset
state “
Pld 0/otL 0
” and the flashing stops.)
●
Display
•
Unset values are indicated as “
Pld 0/otL 0
”.
•
When setup data
C58
is set to 1, PID groups, output limiter group number
items are skipped and not displayed.
NOTE
When a PID group or output limiter group number is not 0 or both are something
other than 0, they use a subfunction. A subfunction cannot be used when a setting
has not been made “
Pld 0/otL 0
”.
Handling Precautions
• When a set value for a PID group number is 0, it is a sequel to a PID
number in a previous segment. When the set value for a PID group
number in the first segment is 0, the set value is 1.
• When a set value for an output limiter group number is 0, it is a sequel
to an output limiter group number in a previous segment. When the set
value for an output limiter group number in the first segment is 0, the set
value is 1.
PROG
SEG
PROFILE
Program
number
Segment
number
Set PID group value
Pattern trend
C O N T R O L
M V O U T L I M I T E R
Set output limiter
group number value
Chapter 8. PROGRAM SETUP