3.5 Control Circuit Wiring
u
Control Circuit Connection Diagram
Refer to
Figure 3.1
on page
77
when wiring terminals on the bypass and drive control circuits.
u
Control Circuit Terminal Block Functions
WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a bypass with
untested control circuits could result in death or serious injury.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting parameter
Z1-01 may change the I/O terminal function automatically from the default setting.
Refer to Application Selection on page 123
to comply may result in death or serious injury.
The functions of the control circuit terminals are shown in
The control circuit terminals on Terminal Board A2 are arranged as shown in
12. SHIELD
11. SHIELD
10. IG24
9. IG24
8. DI-8
7. DI-7
6. DI-6
5. DI-5
4. DI-4
3. DI-3
2. DI-2
1. DI-1
TB2
TB3
4. SHIELD
3. TXRX-
2. TXRX+
1. IG5
TB1
12. DO-10 NO
11. DO-10 C
10. DO-10 NC
9. DO-9 NO
8. DO-9 C
7. DO-9 NC
6. DO-8 NO
5. DO-8 C
4. DO-8 NC
3. DO-7 NO
2. DO-7 C
1. DO-7 NC
Figure 3.18 Control Circuit Terminal Board A2 Arrangement
Table 3.7 Bypass Control Circuit Terminal Board A2
Type
Signal Name
Description
Specification
Digital Inputs
DI-1
Digital Input 1
Dry contact rated, photocoupler sinking input to IG, 24 Vdc 8 mA,
ground fault protected
DI-2
Digital Input 2
DI-3
Digital Input 3
DI-4
Digital Input 4
DI-5
Digital Input 5
DI-6
Digital Input 6
DI-7
Digital Input 7
DI-8
Digital Input 8
IG24
Isolated Ground
Digital Input Common
3.5 Control Circuit Wiring
96
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual