gives an overview of the various features associated with the bypass.
Table 1.1 Control Mode Features
Motor Type
Induction Motors
Comments
Control Mode
V/f
–
Basic Description
V/f control
–
Type of Applications
Motor Type
IM
–
Multi Motor
YES
–
Motor data unknown
YES
–
High Speed Accuracy
–
–
Control
Characteristics
Speed Control Range
1:40
May fluctuate with characteristics and motor
temperature.
Speed Accuracy
±2 to 3%
Speed deviation when operating at constant speed
may fluctuate with characteristics and motor
temperature.
Speed Response
3 Hz (approx.)
Max. frequency of a speed reference signal that the
drive can follow may fluctuate with characteristics
and motor temperature.
Starting Torque
150% at 3 Hz
Starting torque may fluctuate with characteristics
and motor temperature.
Application-Specific
Auto-Tuning
• Energy Saving Tuning
• Line to line resistance
Automatically adjusts parameter settings that
concern electrical characteristics of the motor.
Speed Search
YES
Bi-directional speed detection of a coasting motor
to restart it without stopping.
Energy-Saving Control
YES
Saves energy by always operating the motor at its
maximum efficiency.
Overexcitation
Deceleration
YES
Provides fast deceleration without using a braking
resistor.
Commercial Power Switching
Selection
YES
When the output frequency matches the power
supply frequency (60 Hz), the PWM switching
operation stops and switches to operation with a
direct commercial power supply connection.