Auto-tuning, Types of auto-tuning, Before auto-tuning the drive – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 126: 6 auto-tuning

4.6 Auto-Tuning
u
Types of Auto-Tuning
to select the type of Auto-Tuning that bests suits the application.
n
Auto-Tuning for Induction Motors
This feature automatically sets the V/f pattern and motor parameters E1-oo and E2-oo for an induction motor.
Table 4.14 Types of Auto-Tuning for Induction Motors
Type
Setting
Application Conditions and Benefits
Control
Mode
V/f
Stationary Auto-Tuning for Line-
to-Line Resistance
T1-01 = 2
• The drive is used in V/f Control and other Auto-Tuning selections are not
possible.
• Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and motor has been replaced
with a cable over 50 m long. Assumes Auto-Tuning has already been
performed.
• Should not be used for any vector control modes unless the motor cable has
changed.
YES
Rotational Auto-Tuning for V/f
Control
T1-01 = 3
• Recommended for applications using Speed Estimation Speed Search or using
the Energy Saving function in
V/f Control.
• Assumes motor can rotate while Auto-Tuning is executed. Increases accuracy
for certain functions like torque compensation, slip compensation, Energy
Saving, and Speed Search.
YES
lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting Auto-Tuning.
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer.
Table 4.15 Auto-Tuning Input Data
Input Value
Input Parameter
Unit
Tuning Type (T1-01)
2
Line-to-Line Resistance
3
Rotational for
V/f Control
Motor rated power
T1-02
kW
YES
YES
Motor rated voltage
T1-03
Vac
–
YES
Motor rated current
T1-04
A
YES
YES
Motor rated frequency
T1-05
Hz
–
YES
Number of motor poles
T1-06
-
–
YES
Motor rated Speed
T1-07
r/min
–
YES
Motor iron loss
T1-11
W
–
YES
u
Before Auto-Tuning the Drive
Check the items below before Auto-Tuning the drive.
n
Basic Auto-Tuning Preparations
• Auto-Tuning requires the user to input data from the motor nameplate or motor test report. Make sure this data is available
before Auto-Tuning the drive.
• For best performance, the drive input supply voltage must be at least equal to or greater than the motor rated voltage.
Note:
Better performance is possible when using a motor with a base voltage that is lower than the input supply voltage (20 V for 208 V models
and 40 V for 480 V models). This is particularly important when operating the motor above 90% of base speed, where high torque precision
is required.
• To cancel Auto-Tuning, press the OFF key on the HOA keypad.
• When using a motor contactor, make sure it is closed throughout the Auto-Tuning process.
4.6 Auto-Tuning
126
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual