Setting 4: cooling tower fan application – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 124

No.
Parameter Name
Default Setting
b5-08
PID Primary Delay Time Constant
2 s
b5-13
PID Feedback Low Detection Level
2%
b5-14
PID Feedback Low Detection Time
25 s
C1-01
Acceleration Time 1
60 s
H3-01
Terminal A1 Signal Level Selection
2: 4 to 20 mA
H3-02
Terminal A1 Function Selection
B: PID feedback
H3-10
Terminal A2 Function Selection
16: Differential PID feedback
L5-01
Number of Auto Restart Attempts
10
L6-01
Stall Prevention Selection during Deceleration
5: UL3 at speed agree (Alarm)
o1-07
Second Line Monitor Selection
505: PID Differential Feedback
u
Setting 4: Cooling Tower Fan Application
Table 4.10 Cooling Tower Fan: Parameter Settings
No.
Parameter Name
Default Setting
b1-03
Stopping Method Selection
1: Coast to Stop
b1-04
Reverse Operation Selection
0: Reverse operation enabled
b2-09
Motor Pre-Heat Current 2
10%
C1-01
Acceleration Time 1
60 s
d2-03
Master Speed Reference Lower Limit
30%
H1-07
Multi-Function Digital Input Terminal S7 Function Selection 60: Motor Pre-Heat 1
L5-01
Number of Auto Restart Attempts
10
L6-01
Stall Prevention Selection during Deceleration
5: UL3 at speed agree (Alarm)
u
Setting 5: Cooling Tower Fan with PID Control Application
Table 4.11 Cooling Tower Fan with PID Control: Parameter Settings
No.
Parameter Name
Default Setting
b1-03
Stopping Method Selection
1: Coast to Stop
b1-04
Reverse Operation Selection
0: Reverse operation enabled
b2-09
Motor Pre-Heat Current 2
10%
b5-01
PID Function Setting
1: Output frequency = PID output 1
b5-03
Integral Time Setting (I)
30 s
b5-08
PID Primary Delay Time Constant
2 s
b5-09
PID Output Level Selection
1: Reverse Output
b5-13
PID Feedback Low Detection Level
2%
b5-14
PID Feedback Low Detection Time
25 s
b5-15
PID Sleep Function Start Level
10.8 Hz
b5-16
PID Sleep Delay Time
25.5 s
C1-01
Acceleration Time 1
60 s
d2-03
Master Speed Reference Lower Limit
30%
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
60: Motor Pre-Heat 1
L5-01
Number of Auto Restart Attempts
10
L6-01
Stall Prevention Selection during Deceleration
5: UL3 at speed agree (Alarm)
4.5 Application Selection
124
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual