Setting 4: cooling tower fan application – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 124

background image

No.

Parameter Name

Default Setting

b5-08

PID Primary Delay Time Constant

2 s

b5-13

PID Feedback Low Detection Level

2%

b5-14

PID Feedback Low Detection Time

25 s

C1-01

Acceleration Time 1

60 s

H3-01

Terminal A1 Signal Level Selection

2: 4 to 20 mA

H3-02

Terminal A1 Function Selection

B: PID feedback

H3-10

Terminal A2 Function Selection

16: Differential PID feedback

L5-01

Number of Auto Restart Attempts

10

L6-01

Stall Prevention Selection during Deceleration

5: UL3 at speed agree (Alarm)

o1-07

Second Line Monitor Selection

505: PID Differential Feedback

u

Setting 4: Cooling Tower Fan Application

Table 4.10 Cooling Tower Fan: Parameter Settings

No.

Parameter Name

Default Setting

b1-03

Stopping Method Selection

1: Coast to Stop

b1-04

Reverse Operation Selection

0: Reverse operation enabled

b2-09

Motor Pre-Heat Current 2

10%

C1-01

Acceleration Time 1

60 s

d2-03

Master Speed Reference Lower Limit

30%

H1-07

Multi-Function Digital Input Terminal S7 Function Selection 60: Motor Pre-Heat 1

L5-01

Number of Auto Restart Attempts

10

L6-01

Stall Prevention Selection during Deceleration

5: UL3 at speed agree (Alarm)

u

Setting 5: Cooling Tower Fan with PID Control Application

Table 4.11 Cooling Tower Fan with PID Control: Parameter Settings

No.

Parameter Name

Default Setting

b1-03

Stopping Method Selection

1: Coast to Stop

b1-04

Reverse Operation Selection

0: Reverse operation enabled

b2-09

Motor Pre-Heat Current 2

10%

b5-01

PID Function Setting

1: Output frequency = PID output 1

b5-03

Integral Time Setting (I)

30 s

b5-08

PID Primary Delay Time Constant

2 s

b5-09

PID Output Level Selection

1: Reverse Output

b5-13

PID Feedback Low Detection Level

2%

b5-14

PID Feedback Low Detection Time

25 s

b5-15

PID Sleep Function Start Level

10.8 Hz

b5-16

PID Sleep Delay Time

25.5 s

C1-01

Acceleration Time 1

60 s

d2-03

Master Speed Reference Lower Limit

30%

H1-07

Multi-Function Digital Input Terminal S7 Function Selection

60: Motor Pre-Heat 1

L5-01

Number of Auto Restart Attempts

10

L6-01

Stall Prevention Selection during Deceleration

5: UL3 at speed agree (Alarm)

4.5 Application Selection

124

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual