Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the

number of digits. The setting value is equal to the number of decimal places.

No.

Name

Setting Range

Default

b5-38

PID Setpoint User Display

1 to 60000

Determined by

b5-20

b5-39

PID Setpoint Display Digits

0 to 3

Determined by

b5-20

Setting 0: No Decimal Places
Setting 1: One Decimal Place
Setting 2: Two Decimal Places
Setting 3: Three Decimal Places

n

b5-40: Frequency Reference Monitor Content During PID

Sets the content of the frequency reference monitor display (U1-01) when PID control is active.

No.

Name

Setting Range

Default

b5-40

Frequency Reference Monitor Content During PID

0, 1

0

Setting 0: Frequency Reference after PID

Monitor U1-01 displays the frequency reference increased or reduced for the PID output.

Setting 1: Frequency Reference

Monitor U1-01 displays the frequency reference value.

n

b5-46: PID Setpoint Monitor Unit Selection

Sets the HOA keypad display units in U5-01 and U5-04 when b5-20 is set to 3.

No.

Name

Setting Range

Default

b5-46

PID Setpoint Monitor Unit Selection

0 to 14

0

Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPM (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)

n

b5-47: PID Output Reverse Selection 2

Determines whether a negative PID output reverses the direction of drive operation. When the PID function is used to trim

the frequency reference (b5-01 = 3), this parameter has no effect and the PID output will not be limited

(same as b5-11 = 1).

No.

Name

Setting Range

Default

b5-47

PID Output Reverse Selection 2

0, 1

1

Setting 0: Reverse Disabled

Negative PID output will be limited to 0 and the drive output will be stopped.

5.2 b: Application

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

151

5

Programming