Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 422

Point
No.
Point
Type
Point Name
Factory
Default
(SI Units)
Engr. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Z1000U
Parameter
{28}
LDI
LOC.REM
MON
REMOTE
–
1
0
LOCAL
REMOTE
UB-05
{29}
LDO
DAY.NGT
DAY
–
1
0
NGT
DAY
–
30
LAO
CURRENT
LMT
0
AMPS (A)
0.01/0.1
<1>
0
–
–
E2-01
31
LAO
ACCEL
TIME
0
SEC
0.1
0
–
–
C1-01
32
LAO
DECEL
TIME
0
SEC
0.1
0
–
–
C1-02
33
LDO
LOCK
PANEL
UNLOCK
–
1
0
LOCK
UNLOCK
–
35
<3>
LDO
RUN
ENABLE
STOP
–
1
0
ENABLE
STOP
Bypass DI-2
36
LAO
STALL PRE
RN
90
PCT
1
30
–
–
L3-06
37
LAO
STALL PRE
AC
120
PCT
1
0
–
–
L3-02
38
LAO
FREQ UP
LIM
100
PCT
0.1
0
–
–
d2-01
39
LAO
FREQ LOW
LIM
0
PCT
0.1
0
–
–
d2-02
{40}
LDI
MULTI OUT
1
OFF
–
1
0
ON
OFF
UB-03 (Bit 6)
Bypass DO-7
{41}
LDI
MULTI OUT
2
OFF
–
1
0
ON
OFF
UB-03 (Bit 7)
Bypass DO-8
{42}
LDI
MULTI OUT
3
OFF
–
1
0
ON
OFF
UB-03 (Bit 8)
Bypass DO-9
{43}
LDI
SAFETY
ILOCK
OFF
–
1
0
ON
OFF
UB-05 (Bit 7)
{44}
<4>
LDO
MF INP 1
OFF
–
1
0
ON
OFF
Bypass DI-3
{45}
<4>
LDO
MF INP 2
OFF
–
1
0
ON
OFF
Bypass DI-4
{46}
<4>
LDO
MF INP 3
OFF
–
1
0
ON
OFF
Bypass DI-5
{47}
<4>
LDO
MF INP 4
OFF
–
1
0
ON
OFF
Bypass DI-6
{48}
<4>
LDO
MF INP 5
OFF
–
1
0
ON
OFF
Bypass DI-7
49
LAO
JUMP FREQ
1
0
HZ
0.1
0
–
–
d3-01
50
LAO
JUMP FREQ
2
0
HZ
0.1
0
–
–
d3-02
51
LAO
JUMP FREQ
3
0
HZ
0.1
0
–
–
d3-03
52
LAO
JUMP FREQ
BW
0
HZ
0.1
0
–
–
d3-04
53
LAO
NUM
AUTOSTRT
0
–
1
0
–
–
L5-01
54
LAO
POWER
LOSS RT
0.1
SEC
0.1
0
–
–
L2-02
55
LAO
RUN OP
MODE
1
–
1
0
–
–
Z1-08
56
LAO
REF OP
MODE
1
–
1
0
–
–
Z1-07
57
LAO
OPER DISP
MD
0
–
1
0
–
–
o1-03
{58}
LDI
MF IN 1
MON
OFF
–
1
0
ON
OFF
UB-02 (Bit 2)
Bypass DI-3
{59}
LDI
MF IN 2
MON
OFF
–
1
0
ON
OFF
UB-02 (Bit 3)
Bypass DI-4
E.4 APOGEE FLN Point List Summary
422
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual