Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 87

Table 3.3 Main Input Circuit Wiring Tightening Torques and Wire Gauges Without Option PW
Bypass Model Z1D1
Standard Circuit Breaker Without Option PW
208 Vac
480 Vac
Current Rating (A)
Wire Size Range (AWG)
Tightening Torque (lb. in.)
–
B011
25
14-10
or
8-3/0
50
or
120
–
B014
–
B021
40
D024
–
45
–
B027
50
D030
B034
60
–
B040
80
D046
B052
110
D059
B065
D074
B077
D088
B096
125
D114
–
175
4-4/0
225
D143
B124
200
–
B156
225
D169
B180
400
(1-2) x (2/0-500 kcmil)
(1-2) x 442
D211
–
–
B240
600
–
B032
–
B361
(1-3) x (3/0-500 kcmil)
(1-3) x 450
–
B414
Table 3.4 Motor and Ground Wire Gauges and Tightening Torques
Bypass Model Z1D1
Output Circuit Motor Wiring
Earth Ground Wiring
Motor Overload Relay
Ground Lug
208 Vac
480 Vac
Wire Size Range (AWG)
Tightening Torque
(lb. in.)
Wire Size Range (AWG)
Tightening Torque
(lb. in.)
–
B011
18-8
15
14-10 or 8
or
6-4 or 2
35 or 40
or
45 or 50
–
B014
D024
B021
D030
B027
–
B034
16-2
70
–
B040
D046
–
D059
B052
–
B065
10-1/0
100
D074
B077
D088
B096
6-3/0
200
D114
B124
D143
–
14-2/0
120
D169
B156
6–300 kcmil
275
–
B180
D211
B240
(1-2) x (2-600 kcmil)
(1-2) x 500
–
B302
–
B361
–
B414
(1-3) x (2-600 kcmil)
(1-3) x 500
3.4 Input and Output Power Wiring Connections
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
87
3
Electrical Installation